On the control panel side (front) of the unit, open the front door panel by inserting the key into the latches and unlocking, then depressing the latch buttons to release.
Lift the front door panel to gain access to the front panel, which contains the control panel switch, control panel, and MCCB switch.

On the control panel, turn off the inverters by tapping OFF on the Home page.
Turn the MCCB off by turning the switch to OFF (O).

Locate and remove the three (3) M5 Dome bolts on the left of the front panel and swing to open.

Identify the MCCB adjustment dials.

| E-Gen model | N value | Io value | tr (s) | Ir | Isd |
|---|---|---|---|---|---|
| E-Gen75 | 4P3D | 100 | - | 1 | 1.5 |
| E-Gen150 | 4P3D | 250 | - | 1 | 1.5 |
| E-Gen300 | 4P3D | 400 | - | 1 | 1.5 |
| E-Gen600 | 4P3D | - | 1 | 1 | 1.5 |
E-Gen75
| Dial | Description | Adjustment. |
|---|---|---|
| N | The number of poles. | Do not adjust. All models should be set to 4P3D only. |
| Io | Base rating. | This should be set to the maximum allowable continuous current. Reduce Io first before adjusting Ir. |
| Ir | Long-Time Pickup Current. Long time-delayed trip timer activates if above this value multiplied by Io. This is the continuous current trip rating. | Adjust Ir for fine tuning only after reducing Io. |
| Isd | Short-Time Pickup Current. Short time-delayed trip timer activates if above this value multiplied by Ir. This is the short current spike rating. | Do not adjust. All models should be set to 1.5 only. |

E-Gen150
| Dial | Description | Adjustment. |
|---|---|---|
| N | The number of poles. | Do not adjust. All models should be set to 4P3D only. |
| Io | Base rating. | This should be set to the maximum allowable continuous current. Reduce Io first before adjusting Ir. |
| Ir | Long-Time Pickup Current. Long time-delayed trip timer activates if above this value multiplied by Io. This is the continuous current trip rating. | Adjust Ir for fine tuning only after reducing Io. |
| Isd | Short-Time Pickup Current. Short time-delayed trip timer activates if above this value multiplied by Ir. This is the short current spike rating. | Do not adjust. All models should be set to 1.5 only. |

E-Gen300
| Dial | Description | Adjustment. |
|---|---|---|
| N | The number of poles. | Do not adjust. All models should be set to 4P3D only. |
| Io | Base rating. | This should be set to the maximum allowable continuous current. Reduce Io first before adjusting Ir. |
| Ir | Long-Time Pickup Current. Long time-delayed trip timer activates if above this value multiplied by Io. This is the continuous current trip rating. | Adjust Ir for fine tuning only after reducing Io. |
| Isd | Short-Time Pickup Current. Short time-delayed trip timer activates if above this value multiplied by Ir. This is the short current spike rating. | Do not adjust. All models should be set to 1.5 only. |

E-Gen600
| Dial | Description | Adjustment. |
|---|---|---|
| N | The number of poles. | Do not adjust. All models should be set to 4P3D only. |
| Ir | Long-Time Pickup Current. Long time-delayed trip timer activates if above this value percentage of 800A. This is the continuous current trip rating. | This should be set to the maximum allowable continuous current. |
| tr (s) | Long-Time Delay Setting | Do not adjust. Should be set to 1 only. |
| Isd | Short-Time Pickup Current. Short time-delayed trip timer activates if above this value multiplied by Ir. This is the short current spike rating. | Do not adjust. All models should be set to 1.5 only. |