<aside> ⚡

Compatibility

CranePower_Media_EGen300_Factory_01_3840x2160.jpg

3 months 1 year 5 years
Inspect air filters, replace if required ✓
Check air vents for debris ✓
Inspect inlet and outlet sockets
for damage ✓
Check for any alarm conditions ✓
Check door closes and latches
properly ✓
Ensure machine is not obstructed
and has free airflow ✓
Inspect for any mechanical damage
on the panels ✓
Open access panels and perform visual inspection for debris, water ingress, insects ✓
Inspect Fire Suppression System battery level ✓
Inspect inverter and charger modules and ensure air intake vents are clean and clear of debris ✓
Inspect internal cables and connections for damage or loose connections ✓
Inspect chiller unit, top up coolant if required ✓
Inspect coolant lines and connections for leaks ✓
Inspect 24V UPS for battery health ✓
Replace intake and exhaust air filters ✓
Replace Fire Suppression System battery ✓
Replace controller coin cell battery ✓
Replace 24V UPS battery ✓
Inspect lifting eyelet, replace if necessary ✓